ARGOS surge protective devices of AG2 range are adapted for overvoltage protections of type 2. 

Modular type 2 surge protective device – Imax 40kA – 3P+

40 kA pre-assembled plug in protections –  TT and TNS neutral earthing systems

 385 V networks- Applications levels I and II

Tests standards : EN 61643-11

Certification : TÜV Rheinland

Description

These surge protective devices with a type 2 connection or “C2” (varistors + spark gaps) are recommended for TT and TNS neutral earthing systems. Plug in and pre-assembled in 4 poles with a single terminal for remote monitoring, their installation is straight forward and maintenance of the networks can be done in total safety (isolation tests, …).

Standard applications : Main boards of main and secondary buildings (sites with a low risk level). Distribution boards : second protection level (sites with lightning rods or high level of risk). Protection of sensitive equipments (autocom, alarm or fire centers, private flats, …).

Mounting on symmetrical DIN rail foot (EN 50022).

Technical features  
Reference ARGAG220403858
Class (according to IEC 61643-11 standard) Type 2
Maximum continuous operating voltage AC (L-N) Uc 385V
Maximum operating voltage AC (N-PE)  Uc 255V
Nominal discharge current (8/20us) In 20kA
Maximal discharge current (8/20us) Imax 40kA
Level of protection  Up <1.8kV / 1,5kV
Maximal backup fuse 125A gl
Response time (L-N/N-PE)   tA <25ns / <100ns
Operating temperature  – 40°C ~ + 80°C
Status indicator : in operation / fault Green / red
Connection section (min-max) 4-35mm²
Mounting on Rail DIN 35mm
Cabinet Thermoplastic UL94-V10
Index of protection IP20

Rules of installation and electrical safety : NF C 15-100, IEC 60364 or equivalent national electrical standard.

  • 3+1 (type “C2”) : protection L-N et N-PE (connection of type 2). L: phase. N: neutral. PE: earth.
  • MOV: varistors. GDT: encapsulated spark gaps.
  • EN 61643-11 : tests with protection device against short circuit currents (IEC 61643-1/1998 : without).
  • Maximum calibre of fuses upstream the surge protective devices (circuit breakers : 160A gl).

Modular type 2 surge protective device– Imax 40kA – 1P+N

 40 kA pre assembled plug in protections– TT and TNS neutral earthing systems

 230 V networks- Applications levels I and II

Tests standards : EN 61643-11

These surge protective devices with a type 2 connection or “C2” (varistors + spark gaps) are recommended for TT and TNS neutral earthing systems. Plug in and pre-assembled in 2 poles with a single terminal for remote monitoring, their installation is straight forward and maintenance of the networks can be done in total safety (isolation tests, …).

Standard applications : Distribution boards : second protection level (sites with lightning rods or high level of risk). Protection of sensitive equipments (autocom, alarm or fire centers, private flats, …).

Mounting on symmetrical DIN rail foot (EN 50022).

 

Technical features   
Reference ARGAG220402756
Class (according to IEC 61643-11 standard) Type 2
Maximum continuous operating voltage AC (L-N)  Uc 275V
Maximum operating voltage AC (N-PE)   Uc 255V
Nominal discharge current (8/20us)  In 20kA
Maximal discharge current (8/20us)   Imax 40kA
Level of protection Up <1,5kV
Maximal backup fuse 125A gl
Response time (L-N/N-PE)  tA <25ns / <100ns
Operating temperature  – 40°C ~ + 80°C
Status indicator : in operation / fault Green / red
Connection section (min-max) 4-35mm²
Mounting on Rail DIN 35mm
Cabinet Thermoplastic UL94-V10
Index of protection IP20

Rules of installation and electrical safety : NF C 15-100, IEC 60364 or equivalent national electrical standard.

  • 1+1 (type “C2”) : protection L-N et N-PE (connection of type 2). L : phase. N : neutral. PE : earth.
  • MOV : varistors. GDT: encapsulated spark gaps.
  • EN 61643-11 : tests with protection device against short circuit currents (IEC 61643-1/1998 : without).
  • Maximum calibre of fuses upstream the surge protective devices (circuit breakers : 160A gl).

 

 

Main rules of installation 

 

 

Type 2 surge protective device

Type 2 surge protective device

ARGOS surge protective devices of AG2 range are adapted for overvoltage protections of type 2. 

Modular type 2 surge protective device – Imax 40kA – 3P+

40 kA pre-assembled plug in protections –  TT and TNS neutral earthing systems

 385 V networks- Applications levels I and II

Tests standards : EN 61643-11

Certification : TÜV Rheinland

Description

These surge protective devices with a type 2 connection or “C2” (varistors + spark gaps) are recommended for TT and TNS neutral earthing systems. Plug in and pre-assembled in 4 poles with a single terminal for remote monitoring, their installation is straight forward and maintenance of the networks can be done in total safety (isolation tests, …).

Standard applications : Main boards of main and secondary buildings (sites with a low risk level). Distribution boards : second protection level (sites with lightning rods or high level of risk). Protection of sensitive equipments (autocom, alarm or fire centers, private flats, …).

Mounting on symmetrical DIN rail foot (EN 50022).

Technical features  
Reference ARGAG220403858
Class (according to IEC 61643-11 standard) Type 2
Maximum continuous operating voltage AC (L-N) Uc 385V
Maximum operating voltage AC (N-PE)  Uc 255V
Nominal discharge current (8/20us) In 20kA
Maximal discharge current (8/20us) Imax 40kA
Level of protection  Up <1.8kV / 1,5kV
Maximal backup fuse 125A gl
Response time (L-N/N-PE)   tA <25ns / <100ns
Operating temperature  – 40°C ~ + 80°C
Status indicator : in operation / fault Green / red
Connection section (min-max) 4-35mm²
Mounting on Rail DIN 35mm
Cabinet Thermoplastic UL94-V10
Index of protection IP20

Rules of installation and electrical safety : NF C 15-100, IEC 60364 or equivalent national electrical standard.

  • 3+1 (type “C2”) : protection L-N et N-PE (connection of type 2). L: phase. N: neutral. PE: earth.
  • MOV: varistors. GDT: encapsulated spark gaps.
  • EN 61643-11 : tests with protection device against short circuit currents (IEC 61643-1/1998 : without).
  • Maximum calibre of fuses upstream the surge protective devices (circuit breakers : 160A gl).

Modular type 2 surge protective device– Imax 40kA – 1P+N

 40 kA pre assembled plug in protections– TT and TNS neutral earthing systems

 230 V networks- Applications levels I and II

Tests standards : EN 61643-11

These surge protective devices with a type 2 connection or “C2” (varistors + spark gaps) are recommended for TT and TNS neutral earthing systems. Plug in and pre-assembled in 2 poles with a single terminal for remote monitoring, their installation is straight forward and maintenance of the networks can be done in total safety (isolation tests, …).

Standard applications : Distribution boards : second protection level (sites with lightning rods or high level of risk). Protection of sensitive equipments (autocom, alarm or fire centers, private flats, …).

Mounting on symmetrical DIN rail foot (EN 50022).

 

Technical features   
Reference ARGAG220402756
Class (according to IEC 61643-11 standard) Type 2
Maximum continuous operating voltage AC (L-N)  Uc 275V
Maximum operating voltage AC (N-PE)   Uc 255V
Nominal discharge current (8/20us)  In 20kA
Maximal discharge current (8/20us)   Imax 40kA
Level of protection Up <1,5kV
Maximal backup fuse 125A gl
Response time (L-N/N-PE)  tA <25ns / <100ns
Operating temperature  – 40°C ~ + 80°C
Status indicator : in operation / fault Green / red
Connection section (min-max) 4-35mm²
Mounting on Rail DIN 35mm
Cabinet Thermoplastic UL94-V10
Index of protection IP20

Rules of installation and electrical safety : NF C 15-100, IEC 60364 or equivalent national electrical standard.

  • 1+1 (type “C2”) : protection L-N et N-PE (connection of type 2). L : phase. N : neutral. PE : earth.
  • MOV : varistors. GDT: encapsulated spark gaps.
  • EN 61643-11 : tests with protection device against short circuit currents (IEC 61643-1/1998 : without).
  • Maximum calibre of fuses upstream the surge protective devices (circuit breakers : 160A gl).

 

 

Main rules of installation 

 

 